Programming The Control - Pentair 1.0 Service Manual

Whole house acid neutralizing systems
Table of Contents

Advertisement

HOW TO PROGRAM THE INSTALLER'S LEVEL
KEY BUTTONS:
SCROLL BUTTON
UP ARROW
DOWN ARROW
To begin, verify that the control is in the Service Mode.
Time of Day
GL Remaining
• Press the DOWN ARROW and hold it for 5 seconds; the control will display:
System Check
• Within 10 seconds, enter the following key sequence:
DOWN ARROW
DOWN ARROW
SCROLL BUTTON
DOWN ARROW
The control is now in the Installer's Level. Use the SCROLL BUTTON to advance through the different
settings.
The following settings are available in the Installer's Level:
1. CAPACITY
The control will display:
Capacity: 1200 GL
• Press the UP or DOWN ARROW to change the volume of treated water between regenerations. The
gallons are in increments of 100. The setting range is 100 to 999,999 gallons (maximum limit).
FOR ACID NEUTRALIZERS: A 600 gallon setting is a good starting point for acid neutralizers.
Consistent backwash is very important to maintaining the life of a neutralizer bed.
Press the SCROLL BUTTON to advance to the next setting.