Pid Technology Controller - Siemens SIMATIC ET 200pro FC-2 Operating Instructions Manual

Low voltage converter for the distributed i/o system
Hide thumbs Also See for SIMATIC ET 200pro FC-2:
Table of Contents

Advertisement

Application example
In the following application example, the higher-level control sets the ramp-up and ramp-
down times of the inverter via PROFIBUS.
Figure 7-22
Preconditions
● You have commissioned the communication between the inverter and the control system.
● Free telegram 999 has been set in the inverter and in your higher-level control system.
● The control sends the scaling value to the inverter in PZD 3.
Procedure
1. Set p1138 = 2050[2].
This means that you have interconnected the scaling factor for the ramp-up time with
PZD receive word 3.
2. Set p1139 = 2050[2].
This means that you have interconnected the scaling factor for the ramp-down time with
PZD receive word 3.
The inverter receives the value for scaling the ramp-up and ramp-down times via PZD
receive word 3.
Further information is provided on the Internet:
7.10

PID technology controller

Overview
The technology controller controls process variables, e.g. pressure, temperature, level or
flow.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Application example for changing the ramp-function generator times in operation
Drive control via PROFIBUS and PROFINET (Page 98)
FAQ (https://support.industry.siemens.com/cs/ww/en/view/82604741)
Advanced commissioning
7.10 PID technology controller
145

Advertisement

Table of Contents
loading

Table of Contents