3. When the first of the two times (p1227 or p1228) has elapsed, the inverter issues the
command to close the brake.
4. After the "motor holding brake closing time" p1217, the inverter switches off the motor.
The motor holding brake must close within the time p1217.
After the OFF2 command
Figure 7-9
After the OFF2 command, the inverter issues the signal to immediately close the motor
holding brake, irrespective of the motor speed.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Controlling the motor holding brake after OFF2
Advanced commissioning
7.5 Motor holding brake
109