Installation

4.11 Mounting ET 200pro FC-2 fail-safe devices

Power transmission jumper
The power jumper connector is used to loop-through the main power from one frequency
converter/motor starter to the next converter/motor starter.
The table below shows the assignment of the contacts:
Table 4- 4
Pin
1
2
3
4
4.11
Mounting ET 200pro FC-2 fail-safe devices
In principle, failsafe applications are configured the same as standard applications.
Differences in this regard include:
● A module must be inserted to the left of the frequency converter, via which the inverter
safety functions are controlled:
– Repair switch module F-RSM
– F-Switch
● Only the following modules may be inserted between F-RSM or F-Switch and the inverter:
– 400V switch off module
– all direct or reversing starters
Procedure
Mount them one after the other:
1. Module rack
2. Interface module
3. Bus module for F-RSM or F-Switch
4. Bus module for frequency converters
5. Termination module
6. Connection module for the interface module
56
Power jumper connector
Socket
Assignment
1
Phase L1
2
Phase L2
3
Phase L3
4
Not assigned
PE
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
SIMATIC ET 200pro FC-2 converter