Procedure without enabled safety functions
1. Go online:
2. Click the "Download project to target system" button:
3. Wait until STARTER reports that loading has been completed.
4. To save the data to the non-volatile memory of the inverter, select the "Copy RAM to
ROM" button:
5. Go offline:
You have transferred the settings from the PG to the inverter.
Procedure for enabled safety functions
1. Go online:
2. Click the "Download project to target system" button:
3. Call the screen for the safety functions.
You have transferred the settings from the PG to the inverter.
To activate the safety functions, proceed as follows:
1. Select the "Copy parameter" button.
2. Press the "Activate settings" button.
3. To save the data in the inverter, click the "Copy RAM to ROM" button:
4. Go offline:
5. Switch off the inverter power supply.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
.
.
.
.
.
Backing up data and series commissioning
8.2 Saving settings on a PC
.
.
.
197