Finish Commissioning, Plant Mode "Auto - Siemens RXB Series Basic Documentation

Knx bus communications
Table of Contents

Advertisement

Basic settings
Notes
Plant starting
Action
Plant operation = Auto
Action
28 / 88
Siemens
Building Technologies
Main menu > Commissioning > Communication > Basic settings
Basic settings
Device address:
Dec bus power supp:
Clock time operation:
Master
Rem set clock slave:
Before adjustable values are changed for the first time, the operating lines show
the factory-set values, e.g. device address 255.
The factory-settings are also referred to as default values.
3.2.2

Finish commissioning, plant mode "Auto"

If the plant mode was set to "Plant operation = Off" at the start of commissioning
(see Section 3.2.1), it must be reset to "Plant operation = Auto" when
commissioning is complete.
When commissioning is complete (e.g. after "Basic settings", see the operating
page above), the repeated pressing of the ESC button results in the following
warning:
Caution!
Plant starts
ESC
OK
Acknowledge the display of
display then returns to the main menu.
Before exiting the main menu, press the knob to open the "Plant operation" page.
Main menu
Commissioning...
Time switch...
Room operating mode...
Plant operation...
Plant operation
Preselection:
Auto
State:
Cause:
User request room
Select "Auto" (= enable) on the "Preselection" line and acknowledge by pressing
the knob. Press ESC to return to the start page.
KNX bus communications
Commissioning notes
255
On
Yes
OK
by pressing the knob (the plant is started). The
On
For internal use only
CE1P3127en
2013-04-08