Geographical Zone (Apartment) - Siemens RXB Series Basic Documentation

Knx bus communications
Table of Contents

Advertisement

Definition
Geographical zone
RM...controllers
RM...B controllers
Note
Communication of the
room temperature
For internal use only
Siemens
Building Technologies
7.1.3

Geographical zone (apartment)

The term "Geographical zone (apartment)" is specified by KNX and implies a
building divided into geographical (physical) zones. However, in practice it is
related to the operating strategy, which is defined as follows:
One "Geographical zone (apartment)" consists of a number of buildings or parts
of buildings which are grouped together from an operational point of view and
which obey the following criteria:
Same room operating mode.
Same room temperature (setpoint, actual value).
Based on this definition, the "geographical zone (apartment)" might better be
referred to as an "operating zone".
The "Geographical zone (apartment)" is used together with RM... controllers,
RXB/RXL room controllers, RDG/RDF/RDU room thermostats, and QAW740 room
unit.
Main menu > Commissioning > Communication > Room
Room
Geogr zone (ap):
Time switch op: Autonomous
TS slave (apartm):
Room
Geogr zone (ap):
----
TS slave (apartm):
Time switch op:
Autonomous
Geographical zone (apartment)
RM... default
1
RM... B default
----
Setting values
1...126
The "Room" operating page and some other operating pages for the RM...
controllers (RMU7x0 and RMH769) differ from those for the RM...B controllers
(series B devices).
Communication of the room temperature from the QAW740 to an RM... controller
via "Geogr. zone 5":
QAW740
Room temperature
Room unit
Geogr zone: 5
KNX bus communications
Communication via zone addresses
1
1
----
RM..
Room temperature
Controller
Geogr zone: 5
41 / 88
CE1P3127en
2013-04-08