2.2.2

Power consumption of bus devices

To make the best use of the connectable devices set to "Decentral bus power
supply = Off" and the devices without a bus power supply, it is necessary to
calculate the current requirement from the KNX bus.
Power consumption for Synco devices with "Bus power supply unit = Off".
RMU7x0, RMU7x0B universal controllers
RMH760, RMH760B heating controllers
RMK770 boiler sequence controller
RMB795, RMB795B central control units
RMS705, RMS705B switching & monitoring devices
OZW775 central communication unit
QAX9x3 central apartment unit
Power consumption values for Synco devices without a bus power supply unit:
QAWZ40 room unit
RXB/RXL room controllers
RMZ792 bus operator unit
without external supply
with external AC 24 V supply
OZW771.xx central communication units
OZW772.xx web server
VAV controller GxB181.1E/KN
Room thermostats RDF, RDG, RDU
Room thermostat RDF600KN
Flush-mounted sensor AQR2570
Flush-mounted sensor AQR2576
Room units QMX3.P02, 30, 34
Room units QMX3.P37
Room units QMX3.70, 74
Power consumption values for service interface, coupler and IP router:
OCI700 service interface
Area/line coupler N140/x13
Primary line (main line)
Secondary line (sub-line)
IP router N146 from bus
1)
The Siemens IP router N146 consumes 10 mA from the KNX bus despite the
additional external auxiliary voltage AC/DC 24 V. Power consumption with
auxiliary voltage: 25 mA at DC 24 V, max. 800 mW.
KNX bus communications
Engineering notes
1)
5 mA
5 mA
5 mA
5 mA
5 mA
5 mA
5 mA
7.5 mA
5 mA
45 mA
5 mA
5 mA
5 mA
5 mA
20 mA
5 mA
5 mA
15 mA
7.5 mA
10 mA
15 mA
5 mA
6 mA
8 mA
10 mA
19 / 88
CE1P3127en
2013-04-08