Device Addresses Via Acs; Service Tool Oci700.1 And Acs790 Software; Overview - Siemens RXB Series Basic Documentation

Knx bus communications
Table of Contents

Advertisement

Service tool OCI700.1
OCI700 service
interface
For internal use only
Siemens
Building Technologies
5

Device addresses via ACS

5.1

Service tool OCI700.1 and ACS790 software

5.1.1

Overview

The OCI700.1 service tool is used to commission and diagnose devices in the
Synco, SIGMAGYR and ALBATROS ranges, and to operate plants via the KNX
bus or local process bus (LPB) (see data sheet N5655).
When ordering, use type code OCI700.1. No license is required for operation. The
tool is supplied as a complete kit in a service case:
1.
CD-ROM with
Operating software
Service software
Documentation
2.
OCI700 service interface
3.
USB cable, Type B socket
4.
KNX service cable, RJ45 For Synco devices
5.
LPB service cable, RJ12 For SIGMAGYR and ALBATROS controllers
The OCI700 service interface converts the signals between the USB port on the
PC/laptop and the tool interface on the bus device (RJ45 connection).
There is no need to set parameters for the service interface. Only the central unit
(OCI700-KNX) needs to be selected via the software, after which communication is
established with the device (and other devices on the bus).
KNX service cable
RJ45
connector
Bus
conduit box
RM..
KNX bus communications
Device addresses via ACS
(not illustrated below)
USB
Service
interface
QAW740
PC with
ACS software
RXB
33 / 88
CE1P3127en
2013-04-08

Hide quick links: