To protect the output against electrical shock, use the following residual
current devices:
Fluxpower HE Three phase: DEVICE AS TYPE B (IEC/TR 60755/A2)
Electrical connection data
Power (kVA)
Rectifier
Input Fuses (A)
Bypass
Rectifier
2
)
Input cables (mm
Bypass
2
Onput cables (mm
)
2
Battery cables (mm
)
4.1
TERMINAL BOARDS
Fluxpower HE is provided with terminal boards for the connection of power
cables and of auxiliary connections.
Figure 5:Terminal board Fluxpower HE Three phase 10-15-20 kVA
Figure 6: Terminal board Fluxpower HE Three phase 30 – 40 kVA
10
15
20
Three phase
3x25
3x32
3x32
–
–
–
4x6
4x6
4x10
–
–
–
4x6
4x6
4x10
3x6
3x6
3x6
27
30
40
3x70
3x70
–
–
4x25
4x25
–
–
4x25
4x25
3x16
3x16