3.3.3 ENVIRONMENTAL INSTALLATION CONDITIONS

The air is classified by the EN 60721-3-3 standard (Classification of
environmental parameters and their severities – Stationary use at weather-
protected locations) based on climatic and biological conditions as well as on
mechanically and chemically active substances.
The place of installation must meet specific requirements to ensure
compliance with the conditions for which the UPS was designed.
Climatic conditions according to the technical specification
of Fluxpower HE
Environmental parameter
Minimum operating temperature (°C)
Maximum operating temperature (°C)
Minimum relative humidity (%)
Maximum relative humidity (%)
Condensation
Precipitation with wind (rain, snow, hail, etc.)
Water with an origin other than rain
Ice formation
Classification of biological conditions (EN 60721-3-3)
Environmental
parameter
3B1
a) Flora
No
b) Fauna
No
Class
3B2
Presence of mildew,
fungus, etc.
Presence of rodents and
other animals that are
harmful to products,
excluding termites
3B3
Presence of mildew,
fungus, etc.
Presence of rodents and
other animals that are
harmful to products,
including termites
21
– 10
+ 40
5
95
No
No
No
No