(3) The table below explains the settings of the SLOT switch:
Description of the settings
Setting
Value
Points selected
0
16 points
1
32 points
2
64 points
3
128 points
4
16 points
5
32 points
6
64 points
7
128 points
See Section 7.6, "Data Transfer Modes" for details on how data transfer mode operates.
Note: Do not use these settings. These values are used for maintenance purposes only.
If these values need to be used, thoroughly read Section 8.2, "T/M
(Test/Maintenance Program)," and try them off-line.
(4) The table below explains the settings of the FUNC1 switch:
Description of the settings
Setting
Value
Baud rate
0
125kbps
1
250kbps
2
500kbps
3
Do not use this setting because it is reserved for
future use.
4
125kbps
5
250kbps
6
500kbps
7
Do not use this setting because it is reserved for
future use.
Module information: The module information (module implementation/, digital/analog,
Note: Do not use switch settings 8 through F. The red MNS LED indicator will light
up and the module stops its operation.
Data transfer mode
Normal transfer mode
Analog 4-bit shift mode
Module information control
Without module information
Module information
provided
and fuse blowout detection) is embedded in cyclic communication
data and reported to higher levels.
For details, see Section 7.10, "I/O Error Information (Fuse
Blowout)/Mounting Information Addition Function".
− 18 −
Setting
Description of the settings
Value
8
9
A
B
Do not use these settings as these values are
used for maintenance purposes only.
C
D
E
F
Setting
Description of the settings
Value
8
9
A
B
Do not use these settings as these values are
used for future use.
C
D
E
F

Advertisement

Table of Contents
loading

Table of Contents