Option LED Display
The option has four bicolor, red/green LEDs to relay information about power, communication status, and errors. The
operational states of the LEDs after completion of the power-up diagnostic process are described in
2 seconds for the power-up diagnostic process to complete before verifying the states of the LEDs.
Display
LED
Color
RUN
Green
(Power)
ERR
Red
(Option Error)
COMM
(Communication
Green
Status)
BF
(PROFIBUS-DP
Red
Error)
LED
RUN ERR COMM BF
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
: Flashing / ×: Off
: On /
YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual
Table 4 Option LED States
Operating Status
Status
ON
Power supply ON
OFF
Power supply OFF
ON
Option error
Drive connection
Flashing
error
OFF
Normal operation
Communication
ON
connected
OFF
No data exchange
Waiting for
ON
communication
procedure setting
Communication
Flashing
setting error
OFF
Normal operation
Table 5 LED Operation After Power-up Diagnostic
Communication
Status
Drive has no power.
No power
Option is not properly connected to the
drive or is not receiving enough power.
• Checking
• Option is reading the node address or
connection with
parameter configuration.
the drive
• Waiting for initial input data from
• Waiting for data
master device.
from the master
Option self-
The option is damaged.
diagnostics error
• Problem initializing the drive and the
Problem connecting
option.
to the drive
• Incorrect node address.
Waiting for data
Waiting for data from the master device.
from the master
(Set_Parm_Message or
device
Chk_Cfg_Message)
Incorrect data or
The communication settings in the
option time out
master are set incorrectly.
waiting for data
Sending or
receiving data
Power is supplied to the option, and the option hardware self-diagnostics check
is complete.
• The drive has no power supply.
• Option and drive are not connected properly and/or no power is supplied to
the option.
• An internal, self-diagnostic error occurred in the option.
Self-diagnostic error occurred in the option.
Connection error between option and drive. This includes node address setting
errors to parameter F6-30 on the drive side.
Drive and option are properly connected.
Normal send/receive between the option and the PROFIBUS-DP master.
There is a problem establishing communication between the option and the
PROFIBUS-DP master.
Communication-related parameters are in the process of being set or initialized
by the PROFIBUS-DP master.
Communication parameter error from PROFIBUS-DP master.
LED shuts off when the PROFIBUS-DP master is finished setting
communication-related parameters.
Possible Cause
4 Option Components
Table
Remarks
Solution
Check all wiring to the drive, then turn on the power.
Shut off the drive and make sure the option is
connected properly. Turn the power back on.
Cycle power to the drive. If the LED status does not
change, replace the option.
• Cycle power to the drive. If the LED status does
not change, replace the option.
• Check the node address setting in the drive (F6-10)
• Check master network settings.
• Make sure the master device is operating normally.
• Check terminal resistance settings on the data line.
• Check for problems with the data line and
connector.
• Check if the data line is connected properly to
communication connector CN5.
Check the communication settings in the master.
5. Wait at least