Dosing Settings; Other Settings - Grundfos CIM 200 Functional Profile And User Manual

Modbus for smart digital dosing
Hide thumbs Also See for CIM 200:
Table of Contents

Advertisement

8.6 Dosing settings

Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name
00106
SetSetpointManualHI
00107
SetSetpointManualLO
00108
SetPulseVolumeHI
00109
SetPulseVolumeLO
00110
SetBatchDosingVolumeHI
00111
SetBatchDosingVolumeLO
00112
SetBatchDosingTimeHI
00113
SetBatchDosingTimeLO
00114
SetPressureMax

8.7 Other settings

Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address
Register name
00115
SetOutputRelays
00116
SetAnalogOutput
00117
SetDateTimeYear
00118
SetDateTimeMonth
00119
SetDateTimeDay
00120
SetDateTimeHour
00121
SetDateTimeMinute
00122
SetDateTimeSecond
18
Scale
Description
Setting of the setpoint used in operating mode "Manual".
Can also be set via the pump HMI.
0.1 ml/h
The present value can always be read from ActualSetpointManual (register 00207-
00208).
Setting of the pulse volume used in operating mode "Pulse".
Can also be set via the pump HMI.
1 nl
The present value can always be read from ActualPulseVolume (register 00209-
00210).
Setting of the batch dosing volume used in operating mode "Batch".
Can also be set via the pump HMI.
0.001 ml
The present value can always be read from ActualBatchDosingVolume (register
00211-00212).
Setting of the batch dosing time used in operating mode "Batch".
Can also be set via the pump HMI.
0.1 s
The present value can always be read from ActualBatchDosingTime (register
00213-00214).
Setting of the (relative) pressure alarm limit.
0.1 bar
Can also be set via the pump HMI.
The present value can always be read from ActualPressureMax (register 00215).
Scale
Description
Used to enable and disable the output relays 1 and 2.
A relay has to be set to "Bus control" via the pump HMI if it is to be controllable
from Modbus via the SetOutputRelays register. Via the pump HMI, the relays can
also be individually configured to be of type NO or NC.
Bit 0: Relay 1 control:
0: Not active
Bits
1: Active.
Bit 1: Relay 2 control:
0: Not active
1: Active.
The present status of the output relays can always be read from OutputRelays
(register 00319).
Used to control the analog output signal.
The type of signal (4-20 mA or 0-20 mA) follows the setting of the AnalogMode bit.
The analog output has to be set to "Bus control" via the pump HMI if it is to be
0.001 mA
controllable from Modbus.
The present value of the analog output signal can always be read from
AnalogOutput (register 00317).
Used to set the internal real-time clock (RTC).
Year (from year 2000)
Month [1-12]
Day [1-31]
Hour [0-23]
Minute [0-59]
Second [0-59].
BCD string
Each byte is a binary-coded decimal (BCD) value.
Example:
15:38:00, April 24 2011, is coded with hexadecimal numbers as:
Year = 11 h, Month = 04 h, Day = 24 h, Hour = 15 h, Minute = 38 h, Second = 00 h.
Can also be set via the pump HMI.
The present value of the real-time clock can always be read from the DateTime
status registers 00220-00225.