AW T 2 1 0 P R O F I B U S PA 2 - W I R E T R A N S M I T T E R | C O M/A W T 2 1 0/ P R O F I B U S - E N R E V. A
7

Configuration

Local configuration

The configuration of PROFIBUS communications for an AWT210
transmitter can be set locally using the keypad and menus
however it is recommended that the configuration is set
remotely by a Profibus master.
Menu
Communication
Exit
Select
Menu
Comment
Slave address
Device-specific slave address to identify the transmitter on the network.
Tag Descriptor
String to identify the device (displayed at the top of the operator page)
Ident No . Selector
Selects the ident number: 9750 – Analyzer/3404 - Dev Specific/Adaptation Mode
Manuf ID
Read Only Manufacturer Identification number
Device Type
Read Only Indicates the Profibus PA Device Type
PA Profile
Read Only Indicates the Profibus PA profile version

Integration using GSD

PROFIBUS devices differ with respect to available functionality
and parameters for each device type and manufacturer. In order
to obtain 'Plug-and-Play' configuration for PROFIBUS,
characteristic device communication features such as
manufacturer name, device name, hardware/software versions,
baud rate and the number and nature of inputs/outputs are
defined in an electronic device data sheet known as a GSD
(Generic Station Description) file.
A GSD file is readable ASCII text file that contains both general
and device-specific specifications for communication. Each of
the entries describes a feature supported by a device. By using
keywords, a configuration tool reads the device identification,
the adjustable parameters, the corresponding data type and
the permitted limit values for the configuration of the device
from the GSD. Some keywords are mandatory (for example,
Vendor_Name), others are optional (for example, Sync_Mode_
supported).
Used to configure the communications.
The GSD file for AWT210 transmitters specifies the device
specific Ident No. 3404 and conforms to the PROFIBUS
standard, providing a clear and comprehensive description of
each instrument in a precisely defined format. The description
enables the system configuration tool to use the information
automatically when configuring a PROFIBUS bus system.
The AWT210 GSD file (ABB_3404.gsd) is available for download
from the ABB website at:
www.abb.com/fieldbus
field devices).

AWT210 Profibus data sheet

Item
Device name
Profile ident
support
PNO ID no.
Bus Address
Block types
Physical Layer
Transmission rate
9750 = Analyzer
1Ah (26) = ABB
(follow the link for PROFIBUS DP
Detail
AWT210
9750 – Analyzer, 3404 –
Device Specific, Adaptation Mode,
0D4Ch (3404)
0 to 126 (default = 126)
one Physical Block
four Transducer Blocks,
two AI Function Blocks
In compliance with IEC 61158-2
31.25 kbps
9
Default
126
"AWT210"
Analyzer
3.02