Analog Input Blocks - Slots 5 And 6 - ABB AWT210 Manual

Profibus pa 2-wire transmitter
Hide thumbs Also See for AWT210:
Table of Contents

Advertisement

20
AW T 2 1 0 P R O F I B U S PA 2 - W I R E T R A N S M I T T E R | C O M/A W T 2 1 0/ P R O F I B U S - E N R E V. A
...8 PROFIBUS slots
Analog input blocks – slots 5 and 6
AI_1 mapping is located on slot 5. AI_2 mapping is located on slot 6.
The initial index is 16 and this number must be added to the relative
Index in column index to get the absolute index.
First index (n) = 16
Index
Parameter
(n) = 16
n+0
BLOCK_OBJECT
n+1
ST_REV
n+2
TAG_DESC
n+3
STRATEGY
n+4
ALERT_KEY
n+5
TARGET_MODE
n+6
MODE_BLK
n+7
ALARM_SUM
n+8
BATCH
n+9
NULL_ // reserved by PI
n+10
OUT
n+11
PV_SCALE
n+12
OUT_SCALE
n+13
LIN_TYPE
n+14
CHANNEL
n+15
NULL_ // reserved by PI
n+16
PV_FTIME
n+17
FSAFE_TYPE
n+18
FSAFE_VALUE
n+19
ALARM_HYS
n+20
NULL_ // reserved by PI
n+21
HI_HI_LIM
n+22
NULL_ // reserved by PI
n+23
HI_LIM
n+24
NULL_ // reserved by PI
n+25
LO_LIM
n+26
NULL_ // reserved by PI
n+27
LO_LO_LIM
n+28 to n+29 NULL_ // reserved by PI
n+30
HI_HI_ALM
n+31
HI_ALM
n+32
LO_ALM
n+33
LO_LO_ALM
n+34
SIMULATE
n+35
OUT_UNIT_TEXT
Access
STANDARD PARAMETERS
R
Record
R
RW
RW
RW
RW
R
Record
R
Record
R/W
Record
STANDARD AI BLOCK PARAMETERS
RW
Record
RW
RW
Record
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
R
Record
R
Record
R
Record
R
Record
RW
Record
RW
Data
Type
DS-32
Simple
Unsigned16
Simple
OctetString
Simple
Unsigned16
Simple
Unsigned8
Simple
Unsigned8
DS-37
DS-42
DS-67
DS-101
Array
Float
DS-36
Simple
Unsigned8
Simple
Unsigned16
Simple
Float
Simple
Unsigned8
Simple
Float
Simple
Float
Simple
Float
Simple
Float
Simple
Float
Simple
Float
DS-39
DS-39
DS-39
DS-39
DS-50
Simple
OctetString
Size
Range
(bytes)
20
1
32
2
1
1
Table 6 (page 21)
3
8
10
5
8
0.0 to 100.0 %
11
1
0-Linear
2
1-2
4
0 to 60 s
1
Table 8 (page 21)
4
4
4
4
4
4
16
16
16
16
6
Table 9 (page 21)
16

Advertisement

Table of Contents
loading

Table of Contents