8
AW T 2 1 0 P R O F I B U S PA 2 - W I R E T R A N S M I T T E R | C O M/A W T 2 1 0/ P R O F I B U S - E N R E V. A
...6 Installation
Cable length
Maximum cable length
Maximum spur length (1 device)
Maximum spur length (2 devices)
Maximum spur length (3 devices)
Maximum spur length (4 devices)
Cable specification
The cable lengths in Table 1 apply to cable to the following
specification:
Impedance
Capacitance per unit length
Loop resistance
Core diameter
Core cross section
Non IS installations
9 to 32 V DC
IS installations
9 to 24 V DC
Functional earth
Figure 2 PROFIBUS PA communication module connection overview
1900 m (6233 ft)
120 m (394 ft)
90 m (295 ft)
60 m (197 ft)
30 m (98 ft)
135 to 165 Ω
<30 pf/m
110 Ω/km
0.64 mm
>0.34 mm
2
SW1:
SW2:
Reset to
Write
defaults
protection
ON
OFF
PROFIBUS PA module
connections
(connected internally)
A
B
1
2
3
Network connection
PROFIBUS network connections are made to the terminal block
on the AWT210 Communication module.
WARNING – BODILY INJURY
• Refer to the AWT210 Operating Instruction
(OI/AWT210-EN) before making electrical
connections.
NOTICE
Property damage
When connecting an AWT210 to a PROFIBUS-PA network:
• Use cable that meets PROFIBUS specifications for
reliable communications
• Ensure a PROFIBUS active terminator is fitted to
each end of each bus segment.
• Route data lines clear of the source of any strong
electrical and magnetic fields.
Sensor module connections
1 2 3 4 5 6
A
B
4
5
7
8