Some PACS panels may signal on the LED input (Green LED) when access is not granted. In these cases BZR
should be wired to another output from the PACS panel (most likely the red LED). The PAM will ensure that
the BZR input is not signaled and the LED is signaled in order to interpret the PACS as having provided
access. No configuration change is necessary for this so it is important that the wiring is done with
consideration for the behavior of the PACS panel.

4.6 Connecting to the network

Connect the Ethernet cable between the Ethernet port and the PC, hub or switch. There are two LEDs for the
Ethernet connection; one indicates speed (SPD) and the other indicating Activity (ACT). The ACT LED
(LED5) blinks when there is network activity.
Note:
For Rev A of the PAM (91000ABNNN or 91000ANNNN): Some Gigabit Ethernet Switches may
require setting the port to 100 Mbps or 10 Mbps and/or disabling Energy Efficient Ethernet/"Green"
capability of the port. If the switch is a PoE switch and the PoE port must be used, PoE capability
must be disabled.
For Rev B of the PAM (91000BNNNN or 91000BBNNN): It is still suggested to disable POE capability
on the port used, however is not required. No other restrictions from Rev A apply.

4.7 Connecting to the power supply

Using a small flathead screwdriver (1/8 inch or smaller), connect the Power connector on the pivCLASS
Authentication Module to the power supply.
Connect only to a Listed Access Control / Burglary Power - limited power supply.
Important: Connect the PAM to a power supply having a battery backup or which is plugged into an
Uninterruptable Power Supply (UPS). Power loss during normal operation might result in the
loss of data or, in extreme cases, might render the SD card unbootable.
Install in accordance with NFPA70 (NEC) Local Codes, and authorities having jurisdiction. Follow all National
and Local Codes.
The following table provides the power supply connections for each power connector.
CAUTION
Do not connect to AC. PAM does not support POE Power.
PIN
Power Connector
1
2
3
Connect the PAM to Earth Ground (
18
Installing the module
DC
GND
) using the lug built onto the PAM.
DC Power Connections
+
Not Used
-
PLT-01628, Rev. D.2
January 2019