20.3.2 Connection to Terminal Blocks

External sensor and
IQnomic Plus modules
1 2
3 4
5 6 7 8 9 10 1112 13
1415 16 17 18 19 20
Digital inputs, terminals 5–8, are of extra-low voltage type. Ana-
logue inputs, terminal 37 has an input impedance of 66 k.Ω.
*COMPACT Unit: The designations apply to the right-hand version. In the left-hand version, the sensors change function and designation (the
components are named according to whether they are for supply air or extract air).
Terminal
Function
1,2
Output 1
3,4
Output 2
5,6
Input 1
7,8
Input 2
9,10
Control voltage
11,12,13
Connections for EIA 485
14,15,16, 17 Heat exchanger motor
18,19,20
Rotation monitor sensor
21,22
Supply voltage, H EXCH control
23,24
Supply voltage, control unit
25,26
Supply voltage, outputs 24 V
27,28,29
Damper actuator, change-over damper
(Applies to COMPACT Heat only)
30,31,32
Damper actuator, air recirculation damper
33
Output, fixed power supply: 12 V DC out
34
PWM input for Clean Air Control
35
Measuring zero, GND
36
Output, fixed power supply: 10 V DC out
37
Input, 0–10 V DC, for demand-controlled
control of the airflow or set point displacement
DIL selector switches:
COMPACT Unit, right-hand version: DIL switch 4 must be set to the ON position, the other switches must be set to the OFF position.
COMPACT Unit, left-hand version: DIL switches 1 and 4 must be set to the ON position, the other switches must be set to the OFF position.
COMPACT Top: DIL switch 3 must be set to the ON position, the other switches must be set to the OFF position.
58
www.swegon.com
Memory card for log-
DIL selector switch
ging and upgrading
21 22 2324 2526 272829 303132
Remarks
Select function individually. Independent contact, max. 5 A/AC1, 1A/AC3, 250 V
AC.
Select function individually. Independent contact, max. 5 A/AC1, 1A/AC3, 250 V
AC.
Select function individually.
Select function individually.
Control voltage: 24 V AC, max. permissible load : 28 VA. 9 (G), 10 (G0).
11 communication connection A/RT+, 12 communication connection B/RT–,
13 = GND/COM.
14 Earth, 15 Red, 16 Yellow, 17 Black.
18 Brown, 19 Blue, 20 Black.
36 V AC, in
18 V AC, in
24 V AC, in
27 (G0) Black 24 V AC(-), 28 (G) Red 24 V AC(+), 29 (NO) White 24 V AC out if
active.
30 (G0) Black 24 V AC(-), 31 (G) Red 24 V AC(+), 32 (NO) White 24 V AC out if
active.
12 V DC to GND. Max permissible load: 500 mA
VOC sensor
10 V DC to GND Max. permissible load: 20 mA.
Air quality sensor
Registered design. The company reserves the right to make design changes without prior notice.
Network connection Temperature sensor, supply air
3334353637
Temperature sensor,
outdoor air*
GB.COMPACTUT.170622
Communication,
hand-held micro
terminal
Controller, air heater
Pressure sensor, extract
air fan*
Pressure sensor, supply
air fan*
Temperature sensor,
extract air*