4.3 To Adjust the Pressure Balance

4.3.1 General

The air handling unit is equipped with an adjustment
plate designed for achieving a correct air leakage direction
across the heat exchanger. This prevents the extract air
from being carried over to the supply air.
The pressure balance in the unit should be adjusted when
the ventilation system has been fully installed and all the
air diffusers have been airflow-adjusted as well as for the
supply air and extract air flows that prevail while the air
handling unit is operating normally.
12
www.swegon.com
Adjustment plate
COMPACT Unit
CLOSE
COMPACT Top
Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTUT.170622
OPEN
OPEN