High-Speed Output Wiring - Mitsubishi Electric MELSENSOR Vision Sensor VS20 Series User Manual

Fa sensor
Hide thumbs Also See for MELSENSOR Vision Sensor VS20 Series:
Table of Contents

Advertisement

High-speed output wiring

To connect to the inputs of a sink type programmable controller, connect 'High-speed output 0' to 'High-speed output 3' of a
breakout cable directly to the input terminals of the controller inputs.
When 'High-speed output 0' to 'High-speed output 3' are turned ON, the input terminals are pulled down to 3 V DC or less.
Output common
GND
24 VDC
To connect to the inputs of a source type programmable controller, connect 'High-speed output 0' to 'High-speed output 3' of a
breakout cable directly to the input terminals of the controller inputs.
When 'High-speed output 0' to 'High-speed output 3' are turned ON, the input terminals are pulled up to 21 V DC or more.
Output common
GND
24 VDC
To connect 'High-speed output 0' to 'High-speed output 3'' of a breakout cable to a relay, LED, or similar load, connect the
negative side of the load to 'High-speed output 0' to 'High-speed output 3'' and connect the positive side to 24 V DC.
When 'High-speed output 0' to 'High-speed output 3' are turned ON, the negative side of the load is pulled down to 3 V DC or
less, then 24 V DC is applied to the load.
Use a protection diode for a high inductive load. Connect the anode to a output and connect the cathode to '24 V DC'.
Output common
GND
24 VDC
3 SPECIFICATIONS
20
3.3 I/O Specifications
High-speed output 0
Sink type programmable controller input
Input terminal
GND
24 VDC
High-speed output 0
Source type programmable controller input
Input terminal
GND
24 VDC
High-speed output 0
Load
(Coil, Relay etc.)
Not to exceed 50mA