Victron energy MultiPlus 12/3000/120 – 50 Manual page 37

Extremely powerful sine inverter, battery charger and automatic switch in a compact casing
Table of Contents

Advertisement

5.5.2 Step 2: Other settings
Parellel operation: the remaining settings are not relevant (na) for slaves.
Three Phase or split phase: some of the remaining settings are not relevant for
followers (L2, L3). These settings are imposed on the whole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
ds8-ds7
voltage
14.1
off
off
28.2
56.4
14.4
off
on
28.8
57.6
14.7
on
off
29.4
58.8
15.0
on
on
30.0
60.0
ds6: absorption time 8 or 4 hours
ds5: adaptive charging characteristic
(inactive = fixed absorption time)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency
(the wide input frequency range (45-55Hz) is 'on' by default)
Float
Storage
oltage
voltage
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
(na for L2, L3) on = 8 hours
(na for L2, L3) on = active
(na for L2, L3) on = 50Hz
Suitable for
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV)
Gel MK battery
Gel Victron Deep Discharge
Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
Tubular plate traction batteries
in semi-float mode
AGM spiral cell
Tubular plate traction batteries
in cyclic mode
off = 4 hours
off = inactive
on = active
off = inactive
on = active
off = inactive
on = 120V
off = 115V
off = 60Hz
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multiplus 24/3000/70 – 50

Table of Contents