Victron energy MultiPlus 12/3000/120 – 50 Manual page 22

Extremely powerful sine inverter, battery charger and automatic switch in a compact casing
Table of Contents

Advertisement

5. Configuration
Settings may only be changed by a qualified electrical engineer.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the AC input must be removed.
5.1 Standard settings: ready for use
On delivery, the MultiPlus is set to standard factory values. In general, these settings
are suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for
your batteries! Refer to the manufacturer's documentation, or to
your battery supplier!
Standard MultiPlus factory settings
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-phase
AES (Automatic Economy Switch)
Ground relay
Charger on/ off
Battery charge curve
Charging current
Battery type
Automatic equalisation charging
Absorption voltage
Absorption time
Float voltage
Storage voltage
Repeated absorption time
Absorption repeat interval
Bulk protection
AC input current limit
UPS feature
Dynamic current limiter
WeakAC
BoostFactor
Multi-functional relay
VirtualSwitch
PowerAssist
18
60 Hz
45 - 65 Hz
94 - 143 VAC
120 VAC
stand-alone
off
on
on
Four-stage adaptive with BatterySafe mode
75% of the maximum charging current
Victron Gel Deep Discharge (also suitable for Victron AGM
deep discharge
off
14.4 / 28.8 / 57.6 V
up to 8 hours (depending on bulk time)
13.8 / 27.6 / 55.2 V
13.2 / 26.4 / 52.8V (not adjustable)
1 hour
7 days
on
50A (= adjustable current limit for PowerControl and
PowerAssist functions)
on
off
off
2
alarm function
controls the multi-functional relay
on