Victron energy MultiPlus 12/3000/120 – 50 Manual page 33

Extremely powerful sine inverter, battery charger and automatic switch in a compact casing
Table of Contents

Advertisement

Parallel operation (appendix C)
Step 1: Setting ds2 and ds1 for parallel operation
Master
DS-8 AC input
Set
DS-7 AC input
Set
DS-6 AC input
Set
DS-5 AES
na
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Master
DS-1 Master
The current settings (AC current limitation and charging current) are multiplied by the
number of devices. However, the AC current limitation setting when using a remote
panel will always correspond to the value indicated on the panel and is not multiplied
by the number of devices.
Example: 9kVA parallel system
- If an AC input current limit of 20A is set on the master and the system consists of three devices,
then the effective system current limit will be equal to 3 x 20 = 60A.
- If a 30A panel is connected to the master, the system current limit is adjustable to a maximum of
30A, regardless of the number of devices.
- If the charging current on the master is set to 100% (70A for a MultiPlus 24/3000/70) and the
system consists of three devices, then the effective system charging current is equal to 3 x 70 =
210A.
The settings according to this example (9kVA parallel system with 30A Multi Control Panel) are as
follows:
Slave 1
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
off
DS-2 Slave 1
on
DS-1 Slave 1
Slave 2 (optional)
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
off
DS-2 Slave 2
off
DS-1 Slave 2
off
on
29