Control Unit Output R0; Inputs And Outputs Expansion Board 4583 Output 0 - 1; The 3361 Unit Outputs Re0 - Re1 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
9.2
9.3
9.4
9.5
S1
Supervised (monitored) voltage output, 24V DC
mA (Fuse F6).
As default S0-S1 are set to type "Alarm device", "Intermittent 0.8 /
0.8, normally low, supervised and trigger condition "General fire".
Connections and more information, see drawing 128-22.
See also chapter "Programmable voltage outputs (S0-S1)", page 20.

Control unit output R0

EBL128 has one programmable relay output:
R0
Relay output, NO or NC contacts
As default R0 is set to type "Routing equipment" (Fire brigade tx),
Steady (cont.), normally open and trigger condition "Fire brigade tx".
Connections and more information, see drawing 128-23.
8 relay outputs expansion board 4581
Output 0 – Output 7
Each 4581 board has eight programmable relay outputs:
Output 0
Relay output, NO or NC contacts programmable
Output 1
Relay output, NO or NC contacts programmable
Output 2
Relay output, NO or NC contacts programmable
Output 3
Relay output, NO or NC contacts programmable
Output 4
Relay output, NO or NC contacts programmable
Output 5
Relay output, NO or NC contacts programmable
Output 6
Relay output, NO or NC contacts programmable
Output 7
Relay output, NO or NC contacts programmable
Relay contact ratings: Max. 2A @ 30 V DC.
Connections and more information, see dwg. 128-30.
Inputs and Outputs expansion board 4583
Output 0 – 1
Expansion
board
4583
66
(monitored)
voltage outputs:
Output 0
Supervised (monitored) voltage output, 24V DC
200 mA (Fuse F1).
Output 1
Supervised (monitored) voltage output, 24V DC
200 mA (Fuse F2).
Connections and more information, see drawing 128-33.
See also chapter "Inputs and outputs expansion board 4583", page 28.
The 3361 unit outputs Re0 – Re1
Each 3361 unit has two programmable relay outputs:
Re0 Relay output, NO or NC contacts programmable
Re1 Relay output, NO or NC contacts programmable
68
Relay contacts: max. 1 A @ 30 V DC.
EBL128 Planning Instructions V2.0.x
68
programmable.
has
two
programmable,
70
67
, max. 200
supervised
67
, max.
67
, max.

Hide quick links:

Advertisement

Table of Contents
loading