Normal area
(default)
There is also a
Heater area
Normal area
but the rate-of-rise function (deltaT) will not be used for alarm activation.
15.1
15.1.1
15.1.2
extended in order to reduce false (nuisance) alarms.
A learning function will after a learning period adapt an
Alarm algorithm suitable for the smoke and temperature
conditions in the area where the detector is located.
Alarm algorithms for the following areas can be adapted:
Clean area
(higher sensitivity)
Alarm algorithm
This is similar to the alarm algorithm for the
.
Pulse up – down counter
The detector have a "pulse up – down counter", starting at "0" and
cannot be negative.
Pulse up – down counter for smoke
When the smoke obscuration S (%/m) > the alarm threshold level, "1"
is added to the counter every second.
When S < the alarm threshold level, "2" is subtracted from the counter
every second.
Pulse up – down counter for temperature
When the temperature T (°C) > the alarm threshold level, "3" is added
to the counter every second)
122
EBL128 Planning Instructions V2.0.x
Smoke-steam area
Cooking-welding area
(longer delay time)
(longer delay time &
lower sensitivity)