Programmable inputs

EBL128 has one programmable input (I0). In EBL128 can also be
mounted the Inputs and Outputs expansion board 4583, with five
programmable inputs (Input 0-4) that can be supervised or not
supervised. See chapter "Expansion boards 458x", page 24.
On the COM loop can addressable multipurpose I/O units 3361 be
connected. Each 3361 unit has two programmable inputs (In0/Z and
In1), not supervised.
The different inputs have a bit different dialog boxes for programming
via EBLWin. Information that shall be programmed:
Name (Normally not changed, but used as Interlocking input it is
recommended to add some identification information)
Type ("Trigger condition")
Supervised or not supervised. (Not valid for 3361.)
Logic, Normally open (high resistance, 3K3, when supervised) or
Normally closed (low resistance, 680R, when supervised)
Ext. Fault (Text; only for trigger cond. "External fault")
Ext. time channel Name (only for trigger cond. "External time
channel")
Technical warnings (text).
Activate output (Technical address and Output)
Zone, Address and Text (only for trigger cond. "General fire",
"Pre-warning" and "Zone line input").
Alert Annunciation time channel (only for trigger cond. "Zone
line input" – 3361 In 0).
Disablement time channel (only for trigger cond. "Zone line
input" – 3361 In 0).
Figure 10. The EBLWin "Control unit input" dialog box. The
different trigger conditions ("Type") require different additional
information.
EBL128 Planning Instructions V2.0.x
61