Definitions / Explanations

Definitions / explanations / abbreviations / etc. frequently used or not
explained elsewhere in the document.

PESN AB

Panasonic Eco Solutions Nordic AB

Alarm point

Unit, which can generate a fire alarm, i.e. an analog or conventional
detector, a manual call point, etc.

Smoke detector

One type of analog and conventional smoke detectors is available: the
photo electric (optical) smoke detector.

Sensor

Sensor = Analog detector

Analog detector

Contains an A/D-converter.
("sensor values") for each detector individually. All evaluations and
"decisions" are then made in EBL128, i.e. by advanced alarm
algorithms.
As from version 2.0.x the latest detector generation
(440x) can be used. In the "Advanced mode" the alarm algorithms are
stored in the detector instead of the control unit. Analog detectors are
addressable – an address setting tool is used for address and mode
settings. An analog detector has to be plugged in an ASB.

(Analog) Sensor Base (ASB)

A sensor is plugged in an ASB, which is connected to a COM loop
(see below).

Conventional detector

Detector with two statuses, normal or fire alarm.
contains a closing contact and a series alarm resistor.
plugged in a conventional detector base CDB (see below), which is
connected to a conventional zone line input. Some types are water
proof and are not plugged in any base. An end-of-line device is
connected in the last unit on the conventional zone line.

Conventional Detector Base (CDB)

A conventional detector is plugged in a CDB and connected to a
conventional zone line input.

Addressable

A unit with a built-in address device (e.g. a manual call point). Each
unit is individually identified, handled and indicated in EBL128.
EBL128 Planning Instructions V2.0.x
EBL128 picks up the digital values
10