Control unit properties
Figure 24. The EBLWin "Control unit properties" dialog box.
NOTE!
Default settings in EBLWin might vary depending on
convention.
Control unit properties dialog box
Opens when you add a control unit or via the "Control unit" pop-up
menu (Properties...)
General Information
Control unit number: An EBL128 control unit has to have no. 0.
No other number is allowed.
Name: Normally not changed but can be changed when required.
Configuration
Not valid for EBL128.
MMI board (default):
Printer
Misc.
Configured number of alarm points: EBL128 control unit can only
have 256.
Suppress buzzer during fault from other control units: Not
valid for EBL128.
Use Pre-warning: This check box shall be marked if the pre-
warning detection shall be enabled, i.e. pre-warnings will be
activated. All programmable outputs in the system, with trigger
condition "Pre-warning", will be activated (if not disabled).