System Properties, Page 2 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
17.1.3.5
17.1.4
Alarm delay time (seconds)
Valid for the detectors and zone line inputs with this option selected
128
via EBLWin
.
30 is default. 0-255 seconds is possible. Note, this delay time starts
when the fire alarm normally should have been activated.

System properties, Page 2

Fault latching (default): All faults have to be acknowledged, also
corrected faults.
Checkbox not marked = No fault latching = Not corrected faults
can be acknowledged but corrected faults will automatically be
deleted from the fault list.
Use Daylight Saving:
Australian convention: Forward 1 hour the first Sunday in
October, 02:00  03:00. Backward 1 hour the first Sunday in
April, 03:00  02:00.
New Zealand convention: Forward 1 hour the last Sunday in
September, 02:00  03:00. Backward 1 hour the first Sunday in
April, 03:00  02:00.
All other conventions: According to the current EU regulations,
i.e. forward 1 hour the last Sunday in March, 02:00  03:00.
Backward 1 hour the last Sunday in October, 03:00  02:00.
Checkbox not marked = Daylight saving time is not used.
Button "Silence alarm devices" disables alarm devices:
Function, see page 120. See also Operating Instructions, chapter
"Silence alarm devices". Can be used in all conventions.
Silence Buzzer With Door Switch: If the buzzer in the c.i.e.
shall be silenced when the door is opened, this checkbox shall be
marked. This is a violation to the EN54-2 standard.
Flash LED on MCP: The manual call point (type 3333 / 3339 /
4433 / 4439) built-in LED will flash to indicate communication
with the c.i.e.
Checkbox not marked = This option is disabled, i.e. the LED is
switched off until the call point is operated.
Green polling LED:
Valid for the detectors 440x in Advanced mode only.
The detectors 4400 and 4401 have a green polling LED.
Always off = The green polling LED is not used.
Flash when polled = The green polling LED will be blinking 20
ms / 7 sec. indicating the communication with the c.i.e.
NOTE! When the detector is in test mode the green polling LED
will be turned off until the test mode is turned off.
128
Regarding the Australian and New Zealand conventions the "Alarm
Verification Facility" is valid, see page 103.
134
EBL128 Planning Instructions V2.0.x