Input Units - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.1.1
6.1.1.1
3312FL

Input units

Each COM loop input unit is added and programmed via EBLWin.
Depending on type of unit, regarding:
Technical address (001-255)
Name (normally not changed)
Zone number and Address within the zone
Two-units-dependent fire alarm, i.e. co-incidence alarm (if you
wish / some units only)
Quiet alarm or not
Alert annunciation & Time Channel (if you wish / some units
only)
Disablement & Time Channel (if you wish / some units only)
Alarm text (if you wish)
Regular Alarm algorithm (some units only)
Alternative Alarm algorithm & Time Channel (if you wish / some
units only)
Figure 7. An example of an EBLWin dialog box is the "Analog
photo electric smoke detector 4301/4401 (Normal mode)"
properties dialog box.
Connections, if nothing else is specified, see drawing 128-21.
Analog Sensor Bases (ASB)
3312 Analog Base. An analog detector (Sensor) is to be plugged in
3312. Terminals for ext. LED 2217 / 2218. Prepared for
mechanical lock of the detector. Recess for label holder 3391.
The base has an address label on which the plugged-in
detector's technical address is to be written.
3313 Analog Base. Like 3312 but instead of screw terminals for the
COM loop and ext. LED this base has fast connectors.
3314 Analog Base. Like 3312FL but no connector for ext. LED.
3312F
EBL128 Planning Instructions V2.0.x