Logic; Supervised; Output Signal Period - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
10.2
10.3
10.4

Logic

The logic is set in the EBLWin dialog box "Voltage or Relay Output".
(•) Normally open / low Normally open relay contacts / normally
low voltage output.
( ) Normally closed / high Normally closed relay contacts / normally
high voltage output (24V DC).

Supervised

A voltage output is normally supervised (default). By un-marking this
checkbox the voltage output will be not supervised.
NOTE! A normally high output is not supervised.
See also chapter "Programmable voltage outputs (S0-S1)", page 20.

Output signal period

Each output uses an "Output signal period", which controls the
output's activation. The following are available:
Steady (continuous)
Intermittent 0.8s/0.8s
User defined 1
User defined 2
User defined 3
User defined 4
User defined 5
User defined 6
User defined 7
User defined 8
User defined 1-8 can be built up with type and time.
The following types are available:
Steady (continuous)
Intermittent
One pulse
Steady Delayed Activation
Intermittent Delayed Activation
One pulse Delayed Activation
Steady Delayed De-Activation
The following times are available:
 Delay time (when required)
 Pulse length time (when required)
 Pulse off time (when required)
 De-activation time (when required)
See also chapter "Output Signal Periods", page 146.
EBL128 Planning Instructions V2.0.x
73