Alert Annunciation Units - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.2.2
selected fire alarms can be stored in the unit and will in such a
case be shown, instead of the texts sent from EBL128 for these
alarms. These text messages will be downloaded to the unit via
EBL128. A built-in buzzer will sound like in EBL128. The
buzzer can be silenced and the alarm devices in the installation
can be silenced. They will re-sound for a new alarm. When
there are queued alarms in the system, you can scroll amongst
them and they can be reset. Any fault in the system will be
presented as "General fault in system" and the buzzer will
62
sound.
A Printer 1835 can be mounted in ext. FBP 1826. It
will print all the alarms, including the alarm texts. New S/W
versions can be downloaded directly in the unit. The unit is
power supplied from EBL128 or an ext. power supply.
The unit shall run in S/W mode 1826/28 – 1587, which has the
highest performance with regard to functionality, response time,
ability to store fire alarms, etc. Up to 1200 m cable can be
used.
For more information, see Technical description
MEW00249.
1828 External Fire Brigade Panel (FBP). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly but a key is required to
get access to the push buttons. They are disabled until they are
supposed to be used. The unit shall be wall mounted. Two
compression glands are attached. In all other respects it is like
1826, except that a printer cannot be mounted in 1828.
The unit shall run in S/W mode 1826/28 – 1587, which has the
highest performance with regard to functionality, response time,
ability to store fire alarms, etc. Up to 1200 m cable can be
used.
For more information, see Technical description
MEW00249.
1835 Printer. Can be mounted in the External Fire Brigade Panel
1826. It will print all the alarms, including the alarm texts.

Alert Annunciation Units

When the Alert Annunciation (AA) function shall be used in system
EBL128, a unit is required for the related manoeuvres, i.e. to
acknowledge / reset the AA alarms. For a detailed description of the
Alert Annunciation function, see chapter "Alert Annunciation", page
105.
1735 Alert Annunciation Unit (AAU). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
62
Not valid for the Swedish convention (SBF).
EBL128 Planning Instructions V2.0.x
54

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents