Alarm Devices (Addressable) - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.1.3
NORMAL mode: Used for 3364 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 174.

Alarm devices (addressable)

3377 Addressable siren. Replaced with 4477, see below. The siren is
connected directly to the COM loop. It is power supplied via
the COM loop, i.e. the number of sirens is depending on the
type and number of other units connected to the COM loop.
Red ABS plastic housing. Three sound types (tones) and three
priority levels are available. For each level an output control
expression and a sound type is programmed (via EBLWin). For
more technical data, see the Product Leaflet.
The technical address is set with Address setting tool 3314 /
4414. The siren has an address label on which the programmed
technical address is to be written.
The Address setting tool is also used for mode setting:
NORMAL mode: Used for 3377 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 174.
4477 Addressable siren. Replaces 3377, see above. 4477 is like the
3377 unit but it also has a built-in short circuit isolator. (The
function is described at page 49.) The isolator does not use any
COM loop address.
The technical address is set with Address setting tool 3314 /
4414. The siren has an address label on which the programmed
technical address is to be written.
The Address setting tool is also used for mode setting:
NORMAL mode: 4477 with the built-in isolator in use.
2330 mode: 4477 with the built-in isolator not in use. 4477
replaces a 3377 unit.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 174.
3379 Addressable sounder base.
(3312) mounted together with a sounder. 3379 is mounted in
the ceiling. An analog detector can be plugged in the base,
which has screw terminals for the COM loop and an ext. LED
(2218).
Prepared for mechanical lock of the detector - if
required.
Recess for label holder (3391).
supplied via the COM loop, i.e. the number of sounder bases is
depending on the type and number of other units connected to
52
the COM loop
. Three sound types (tones) and three priority
52
The number of 3377 + 3378/3379 + 4477 units must be < 50.
53
This unit has replaced the Sounder base 3378.
EBL128 Planning Instructions V2.0.x
53
3379 consists of an analog base
46
52
3379 is power