Counting operating mode (CNT)
4.2 Parameters/address space
4.2.3

Explanation of parameters

Operating mode
Selection of the operating mode in which all of the module's channels are operated.
● DI (Page 15) / Oversampling (Page 53)
● Counting
When configuring with HSP0229 for STEP 7 or with a GSD file, the operating mode is
specified by selecting the module name.
Diagnostics: No supply voltage L+
Enabling of the diagnostics for no or insufficient supply voltage L+.
Diagnostics: Short-circuit to ground
Enabling of the diagnostics if a short-circuit of the actuator supply to ground occurs.
Channel activated
Determines whether a channel is enabled or disabled. If a digital input is disabled, the
module ignores its signals.
Input delay
You use this parameter to suppress signal interferences. The module only detects changes
to the signal if the changed signal is constantly pending longer than the set input delay time.
Note
If you select the "0.05 ms" value range for the input delay, you have to use shielded cables
for connection of the digital inputs.
Reaction to violation of a counting limit
Selection of the reaction to violation of the counter high limit in the upward direction or the
counter low limit in the downward direction:
● Stop counting:
After a counting limit is violated, the internal gate is closed. This stops the counting
process. The counter value is set to the opposite counting limit. To restart counting, you
must close and reopen the software/hardware gate.
● Continue counting:
After a counting limit is violated, the counter value is set to the opposite counting limit and
counting continues.
38
Digital input module DI 8x24VDC HS (6ES7131-6BF00-0DA0)
Equipment Manual, 11/2019, A5E35243810-AD