Expert" Default Parameters; Start-Up; Verifying The Diagnostic Leds; Setup - FAAC B680H Manual

Hide thumbs Also See for B680H:
Table of Contents

Advertisement

6.4 "Expert" default parameters

The following table contains the pre-defined settings that characterize
the various operation logics.
Step
A
A1
E
01
Y
Y
N
02
N
N
N
03
N
N
N
04
N
N
N
05
N
N
Y
06
N
N
Y
07
N
N
N
08
N
N
N
09
N
N
N
10
N
N
N
11
N
N
N
12
N
N
N
13
N
N
N
14
N
N
N
15
N
N
N
16
N
N
N
17
N
Y
N
18
N
Y
N
19
N
N
N
20
N
Y
N
21
N
Y
N
22
N
N
N
23
N
N
N
24
N
N
N
25
N
N
N
26
N
N
N
27
N
N
N
28
N
N
N
29
N
N
N
30
N
N
N

7. START-UP

7.1 Verifying the diagnostic LEDs

Before starting the operator verify that the status of the diagnostic
LEDs corresponds to the logic. Said status must coincide with the
indications in Fig. 27, which reflects that of an operator in CLOSED
position and ready to open.
The FSW, STOP and EMR LEDs are safety inputs with
NC contacts, therefore the related LEDs must be ON
when the automated system is at rest, and go off when 
the device connected is engaged.
The OPEN and CLOSE inputs are NO contact inputs,
therefore the related LEDs must be OFF when the
automated system is at rest, and go on when the device
connected is active.
The BUS status must correspond to DL2 (green) on
steady  and  DL1  (red)  off.  The  BUS 
menu of the Basic configuration must 
display the indication shown to the
side confirming the fact that there are 
no engaged photocells or active pulse
generators.
P
PA
Cn
Ca
C
N
Y
N
Y
N
Y
Y
Y
Y
Y
N
N
N
N
N
N
N
N
N
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Y
N
N
N
N
N
Y
Y
N
N
N
N
N
N
N
N
Y
Y
Y
Y
N
N
N
N
N
N
Y
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
Y
Y
N
N
N
Y
Y
Y
Y
N
Y
Y
Y
Y
N
N
N
N
N
N
Y
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Y
Y
N
Fig. 27
M2 M1A
M1
DL15
J11
ENCODER
DL1 DL2
J6
J1
3 4 5 6 7 8 9 10 11
1 2

7.2 Setup

Before being put into operation, the E680 board requires a setup
procedure during which the automated system determines the rotation
angle of the beam and consequently its travel. These measurements
allow correct management of motor decelerations and acceleration
ramps.
At first start-up the board will signal the need for a setup 
cycle, by displaying a flashing 
For setup, proceed as follows:
1.
Using the parameter "Mt" in Basic configuration mode, check that
the opening / closing movement corresponds to the pressed key
(+ opens | - closes); if not, go to the motor wiring and reverse
the two conductors L1 and L3, as shown below.
2.
Bring the arm to the fully closed position with the "Mt" parameter
of the Base configuration level or by operating the manual release
device as indicated in Par. 5.
3.
Access Base programming and repeatedly press the F button
until you reach the parameter
at the same time until the operator's arm begins opening slowly,
then release the buttons.
During setup, a flashing -- indication will appear on the 
display.
4.
Upon reaching the fully open position, the operator will stop
automatically.
5.
The operator will then begin the beam closing movement.
6.
Upon reaching the closed position, the operator will stop
automatically.
7.
Press the F button to exit the procedure, and confirm you wish
to save the data with the parameter
of the operator shown on the display is
arm is in the closed position. If the arm is open and the display
00
is showing
, check / adjust the correct direction of movement
of the motor again as in step 1 of the procedure.
L1
M
L2
L3

8. TESTING THE AUTOMATED SYSTEM

Once programming is completed, verify that the system is operating
correctly and that the safety devices work properly, conforming to the
current safety standards.
30
J10
BATTERY
J14
DISP1
SW4
SW5
-
+
F
SW1 SW2 SW3
J15
J2
J3
12 13 14 15 16 17 18 19 20 21
22 23
S0
.
tL
, then press the + and - buttons
St
. Check that the status
00
(closed) and that the
L3
L2
L1
J13
J12
J16
OUT5
OUT6
J4
2 2
4 5 6 7
2 2
M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents