Troubleshooting; Specifications - UTC Fire and Security Interlogix ATS125 Series Installation Sheet

Four-door dgp
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
#
Menu
10.
To Local Devices
Note: CARD FORMAT only can be configured via management
software.
See also Programming Map in Figure 10.
Initialise Database
Initialise the four-door DGP on initial power up only. This is
done via menu option 3, Initialise database.
Caution:
All programming and settings will be reset to factory
defaults. Factory defaults are listed in the ATS125x
programming guide.
Poll connected RASs
Go to menu 1, DGP options.
Set or select the following options:
1.
Enter RASs connected to be polled.
2.
Enter LCD RAS connected.
For more details on how to program the ATS125x four-door
DGP refer to the ATS125x Programming Guide.

Troubleshooting

ATS system data bus indicator LED's
Rx1
The yellow Rx1 LED flashes to indicate polling data is
received on the system data bus from the panel. If the Led
does not flash, the control panel is not operational or the
bus is faulty
Check that DGP is powered correctly.
Check wiring DGP data bus connections.
Tx1
The red Tx1 LED flashes to indicate the DGP is replying to
polling from the control panel. If the Rx1 LED flashes but
the Tx1 LED does not, the DGP is not programmed to be
polled in the control panel or has a wrong address.
Check if the DGP connected to the data bus has
correct address.
Check that the DGP is being polled (Advisor Master
control panel menu 19.4).
Four-door DGP local data bus indicator LEDs
Tx
The red Tx LED flashes when the ATS125x is polling
remote devices (readers/interfaces) on the local databus.
Tx LED should always be active.
Rx
The yellow Rx LED flashes to indicate remote devices reply
to polling.
If the LED does not flash, the RASs are not programmed to
be polled, addressed incorrectly or the bus is faulty.
Check that RASs are powered correctly.
Check wiring RAS data bus connections.
Check that the RASs (readers/interfaces) are polled
(ATS125x menu 1.4 "Poll RAS").
Check that RASs are addressed correctly.
14 / 56
Description
Enables you to access the remote
devices on the local databus.

Specifications

General specifications
End of line resistor
(Other: 10 kΩ, 2 %, 0.25 W; 2.2 kΩ, 2%,
Housing
PCB
Colour
Operating
temperature
Humidity
IP protection grade
Mains power specifications
230 V~ 10%, 50 Hz 10%, 129 VA max.
Mains input voltage
Current consumption
at 230 V~
Main board supply
voltage (J17)
Power supply specifications
13.8 0.2 V
Power supply voltage
Power supply current
4.0 A max. at 13.8
Auxiliary power
output
Note: Maximum permanent current to power
devices external to the control equipment in
the absence of alarm conditions.
13.8 0.2 V
Battery power output
Battery type
Max. battery capacity
ATS1251: 1 x 26 Ah
ATS1253: 1 x 7.2
or 1 x 18 Ah
Main board
consumption
Remaining current
3.9 A at 13.8 V
Notes:
Remaining current means all available current that can be used
for the following: Auxiliary power (incl. switched), Battery charge,
Lock power and Local comms power. You can distribute the total
available current over the terminals as long as the maximum
remaining current and fuse rating for each output is respected.
The needed battery current is dependant on the approval grade.
See "Auxiliary current and battery capacity" on page 15 for
determining which current should be reserved for charging the
battery. Note that Auxiliary power, Lock power and Local comms
power is limited by the battery current.
For the 12 V variant 3900 mA can be distributed. Higher current
value drives the power supply into current limit.
For the 24 V variant 1600 mA can be distributed over 27.6 V
contacts (Locks and Battery) and 1000 mA can be distributed
over the 13.8 V contacts (Auxiliary power incl. Switched and the
Local Comms).
Fuses
F1: Battery 1
F2: Auxiliary power
ATS1251
ATS1252
ATS1253
ATS1254
Default: 4.7 kΩ, 2 %, 0.25 W
0.25 W)
See Table 1 on page 9
202 x 218 x 48 mm
Beige
−10 to +55°C
95% non condensing
IP30
560 mA max.
30 V~ typical
27.6 0.2 V
1.6 A max at 27.6 V
0.2 V
+ 1.1 A max at 13.8 V
13.8 0.2 V, 2 A max.
27.6 0.2 V
Lead acid rechargeable
ATS1252: 2 x 26 Ah
ATS1254: 2 x 7.2 Ah
100 mA at 13.8 0.2 V
1.6 A max at 27.6 V
+1 A max at 13.8 V
5 A, Fast 20x5
1 A, Fast 20x5
P/N 1070341 • REV 2.0 • ISS 22FEB11