5| Compressor assembly

5.1 Setting up

Transport and suspension unit on the eyebolt (Fig. 12, F14 to F16) or direct on the discharge
line valve (Fig. 11, F2 to F5).
D
GB
Fig. 11
F
Fittings (e.g. pipe holders, additional units etc.) on the compressor are permissible only
E
following consultation with Bock.
Setup on an even surface or frame with sufficient load-bearing capacity. Use all 4 fastening
points.
Correct setup of the compressor and mounting of the belt drive are decisive for running comfort,
operating safety and the service life of the compressor.
3
Fig. 13
Fig. 14
Fig. 15
12
INFO!
New compressors are factory-filled with inert gas (3 bar nitrogen).
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
WARNING! Move compressors only with hoists that have adequate load-bearing
capacity.
2
Provide adequate clearance for maintenance work.
Provide adequate ventilation for the drive motor.
Do not use in a dusty, damp atmosphere or a combustible
environment.
Set up on an even surface or frame with sufficient load-bearing
capacity.
Compressors and drive motors are basically rigid and should be
mounted together on a base frame.
Fig. 12
1
F
E
D