4| Compressor assembly
4.1 Storage and transport
?
4.2 Setting up
3
D
GB
F
E
I
Ru
4.3 Pipe connections
ung
12
Zeichn.-Nr.
Teile-Nr.
x.xxxx-xxxxx.x
INFO
New compressors are factory-filled with inert gas (3 bar nitrogen).
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air. Check the compressor for transport
damage before starting any work.
Storage at (-30°C) - (+70°C), maximum permissible relative humidity
10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Use transport eyelet.
Do not lift manually!
Use lifting gear!
ATTENTION Attachments (e.g. pipe holders, additional units, fastening parts,
etc.) directly to the compressor are not permissible!
2
Provide adequate clearance for maintenance work.
Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Setup on an even surface or frame with sufficient load-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
Sun protection: If the compressor is set up outdoors, it has
to be protected from direct sunlight.
ATTENTION Damage possible.
Do not solder as long as the compressor is under pressure.
Superheating can damage the valve. Remove the pipe supports
therefore from the valve for soldering and accordingly cool the
valve body during and after soldering.
Only solder using inert gas to inhibit oxidation products (scale).