General Safety Instructions; Additional Safety Instructions Nh; Intended Use - GEA F Series Assembly Instructions Manual

Bock compressors
Table of Contents

Advertisement

1 | Safety

1.3 General safety instructions

DANGER!
WARNING!

1.4 Additional safety instructions NH

NH
ATTENTION! • High toxicity, intense odour (MAK 50 ppm)
3

1.5 Intended use

These assembly instructions describe the standard version of the compressor named in the title
and NH
manufactured by Bock. The Bock refrigerating compressor are intended for installation in
3
a machine (within the EU according to the EU Directives 2006/42/EC Machinery Directive, 97/23/EC
Pressure Equipment Directive).
Commissioning is permissible only if the compressor has been installed in accordance with these as-
sembly instructions and the entire system into which it is integrated has been inspected and approved
in accordance with legal regulations.
Only the refrigerant specified in these instructions may be used.
Any other use of the compressor is prohibited!
WARNING! The compressor may not be used in potentially explosive
• Refrigerating compressors are pressurised machines and as such
call for heightened caution and care in handling.
The maximum permissible overpressure must not be exceeded,
even for testing purposes.
• Risk of burns! Depending on the operating conditions, surface
temperatures of over 60°C on the discharge side or below 0°C on
the suction side can be reached.
3
• Explosive between 15 and 30 vol. % in the air. Due to the high
ignition energy and temperature, the risk of explosion, however,
is rated as low. So there are no special explosion protection
measures are required.
• However, the national safety regulations, accident prevention
regulations, technical regulations as well as specific regulations
(EN 378 etc.) must be observed.
• NH
steam is lighter than air and therefore disperses upwards.
3
• All key directives are summarised in the area for the AiF research
project 9404B "Safety of ammonia refrigeration systems".
• NH
corrodes copper materials and non-ferrous metals and is
3
incompatible with a number of plastics.
• Proof of personnel's specific expertise for installation,
commissioning, operation and service.
environments!
D
GB
F
E
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents