Creating An As Program - Siemens SITOP PSU8200 Manual

Integration of a sitop 24 v power supply in pcs 7
Hide thumbs Also See for SITOP PSU8200:
Table of Contents

Advertisement

5 Uninterruptible 24 V power supply
5.2.3

Creating an AS program

Proceed as follows:
1. Drag process tag type "SITOP" to the desired folder in the technological
hierarchy and rename it. (1)
Figure 5-14:
2. Open the plan and carry out the modifications below for the input signal to
monitor buffering mode (Rel. 1):
Rename the monitoring block (2) to match its use. Here, the system
monitors the signal for buffering mode
Interconnect input "PV_In" with the corresponding symbol of the external
peripherals (3).
At the "Color" input (4) of the monitoring block, parameterize the value
"16#2". This is so that the system displays the value in yellow in the
faceplate in accordance with a warning.
Figure 5-15:
3
3. Copy interconnected blocks "Pcs7DiIn" and "MonDiL" to the clipboard and
paste them into the CFC plan again. Carry out the modifications below for
monitoring the battery status (Rel. 2):
Integration of a SITOP 24V power supply in PCS 7
Entry ID: 10948108,
V3.2,
01/2019
1
2
4
40