6.3 Derating data

Article No.
Recommended cable cross-section for 500 V
- line cable
- motor cable
3)
Recommended cable cross-section for 690 V
- line cable
- motor cable
3)
Recommended cable cross-section for 500 V
- DC link infeed (2/3 converter power)
Recommended cable cross-section for 690 V
- DC link infeed (2/3 converter power)
Tightening torque for line, motor, DC link, and
ground cable
Dimensions: Width x height x depth [mm]
Weight
The line supply must be capable of supplying the minimum short-circuit current so that the fuses rupture and conse-
1)
quential damage is avoided.
Note: If the minimum short-circuit current is not reached, the rupture time for the fuses increases, which may result in
consequential damage.
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
2)
The motor cables must be evenly distributed at both connection chambers.
3)
6.3
Derating data
6.3.1

Derating factor of the output current as a function of the operating temperature

Figure 6-3
82
6SL3310-
1PG35-8AA0
2 x 240 mm
2 x 185 mm²
2 x 240 mm
2 x 185 mm²
2 x 185 mm
2 x 150 mm
50 Nm / 443 lbf in
801 x 1621 x 393
Derating factor of the output current as a function of the operating temperature
1PG36-5AA0
3 x 185 mm
2
2 x 240 mm²
3 x 150 mm
2
2 x 240 mm²
2 x 185 mm
2
2 x 185 mm
2
50 Nm / 443 lbf in
801 x 1621 x 393
234 kg
234 kg
Hardware Installation Manual, 10/2016, A5E32844552B AD
1PG37-2AA0
3 x 185 mm
2
2
2 x 240 mm²
3 x 185 mm
2
2
2 x 240 mm²
2 x 240 mm
2
2
2 x 185 mm
2
2
50 Nm / 443 lbf in
801 x 1621 x 393
244 kg
Power Module PM330