8 Power supply system SITOP PSU8600 redundant
Proceed as follows:
1. Make sure that the devices are on the same physical network as the
configuration computer.
2. In the SIMATIC Manager, execute the menu command "Target system > Edit
Ethernet Node".
3. In the "Edit Ethernet Node" dialog, click on the "Browse" pushbutton (1) in the
"Ethernet Node" area.
4. In the "Browse Network" dialog, choose the PSU8600 from the list of nodes
and click on "OK" to confirm your selection.
5. Edit the IP address to match your network configuration and click on the
"Assign IP Configuration" pushbutton (2).
6. Edit the device name and click on the "Assign Name" pushbutton (3).
7. Repeat steps 3 to 6 for the second power supply unit.
8. Close the dialog again.
Figure 8-2
Integration of a SITOP 24V power supply in PCS 7
Entry ID: 10948108,
V3.2,
01/2019