Siemens SITOP PSU8200 Manual page 74

Integration of a sitop 24 v power supply in pcs 7
Hide thumbs Also See for SITOP PSU8200:
Table of Contents

Advertisement

8 Power supply system SITOP PSU8600 redundant
Configuring symbols
To interconnect the driver block of the control program with a symbolic address at a
later time, parameterize the I/O addresses of both basic modules using symbols.
Proceed as follows:
1. Select the first PSU8600 in the hardware configuration.
2. Highlight module "PSU8600 3ph ..." on slot 0.2 and execute menu command
"Edit > Symbols...".
3. Parameterize a symbolic name (1) on the first input word.
4. Repeat steps 1 to 3 for the redundant PSU8600.
5. Compile and load the hardware configuration.
Figure 8-4
Setting the SITOP PSU8600 parameters (commissioning)
In the HW configuration for the PSU8600, you can set general parameters,
parameters for R F energy and the output parameters of the basic module's and
the expansion module's 24 V outputs.
You can find more detailed information on the different parameters in the "SITOP
PSU8600" manual at the following link:
https://support.industry.siemens.com/cs/ww/en/view/105867947
Proceed as follows:
1. Select the PSU8600 (1) in the hardware configuration.
2. Open the properties of the "PSU8600 3ph" module (2) on slot 0.1 by double-
clicking.
3. Switch to the "Parameters" tab and set the parameters (3) as desired.
4. Open the properties of the 24 V output (4) and set the parameters of the
outputs as desired.
5. Be sure to parameterize the properties of both PSUs identically.
6. Compile and load the hardware configuration.
Integration of a SITOP 24V power supply in PCS 7
Entry ID: 10948108,
V3.2,
1
01/2019
1
74

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop pse202uSitop psu8600Sitop pse200uSitop ups1600