Decommissioning; Quality Assurance - Growatt MAC 30KTL3-X LV Installation & Operation Manual

Hide thumbs Also See for MAC 30KTL3-X LV:
Table of Contents

Advertisement

General Data
Dimensions (W / H / D)
Weight
Operating temperature
range
Noise emission (typical)
Relative humidity
Highest Altitude
Self-Consumption night
Topology
Cooling concept
Environmental
Protection Rating
Warranty:
Certificates and
approvals
Safety /EMC

11. Decommissioning

If the inverter does not operate in the future, it needs to be properly disposing. The steps are as follows:
1. Disconnect the external AC short circuit and prevent reconnection due to misoperation.
2. Turn the DC switch to "OFF" position.
3. Wait at least 5 minutes until the internal capacitor discharge is completed.
4. Disconnect the AC connector.
5. Disconnect DC connector.
6. Remove the inverter from the wall.
7. Disposing of the inverter.

12. Quality assurance

Please refer to related file
680*508*281 mm
–25° C ... +60° C (derating over 45° C)
≤55dB(A)
0~100%
4000m
Transformerless
Fan cool
5 years/10years(Option)
EN 61000-3, EN 61000-6, EN/IEC 62109-1, EN/IEC 62109-2,
IEC 60529
56 / 57
编号:GR-UM-C -00
52kg
< 1W
IP65