9.2 Configuration of the display (optional)
Select [Uni] and set the unit of measurement:
[°C] or [°F]
Select [diS] and set the update rate and orientation of the display:
-
[d1]: Update of the measured values every 50 ms
-
[d2]: Update of the measured values every 200 ms
-
[d3]: Update of the measured values every 600 ms
-
[rd1], [rd2], [rd3]: Display as for d1, d2, d3; rotated by 180°
-
[OFF]: The display is switched off in the operating mode
9.3. Setting of the output signals for OUT1
9.3.1 Setting of the output function
Select [OU1]and set the function:
-
[Hno] = Hysteresis function / normally open
-
[Hnc] = Hysteresis function / normally closed
-
[Fno] = Window function / normally open
-
[Fnc] = Window function / normally closed
9.3.2 Setting of the switching limits
Select [SP1] and set the value at which the output switches
Select [rP1] and set the value at which the output switches off
rP1 is always smaller than SP1 The unit only accepts values which are
lower than the value for SP1
9.4 Setting of the output signals for OUT2
9.4.1 Setting of the output function
Select [OU2] ] and set the function:
-
[I] = temperature-proportional current signal (4...20 mA)
-
[U] = temperature-proportional voltage signal (0...10 )
9.4.2 Scaling of the analogue value
Select [ASP] and set the measured value at which 4 mA / 0 V is pro-
vided
Select [AEP] and set the measured value at which 20 mA / 10 V is
provided
Minimum difference between ASP and AEP = 5 K