IFM Efector600 TN2531 Operating Instructions Manual page 11

Electronic temperature sensor
Table of Contents

Advertisement

8.2 Explanation of the menu
SP1/rP1
Upper / lower limit value for system temperature at which OUT1 switches
OU1
Output function for OUT1:
Switching signal for the temperature limit values: Hysteresis function [H ] or
window function [F ], either normally open [ no] or normally closed [ nc]
OU2
Output function for OUT2:
Analogue signal: 420 mA [I] or 010 V [U]
ASP
Analogue start value for temperature
AEP
Analogue end value for temperature
EF
Extended functions / opening of menu level 2
HI Maximum value memory for system temperature
LO Minimum value memory for system temperature
COF Zero-point calibration
dS1 Switch-on delay for OUT1
dr1 Reset delay for OUT1
FOU1 Behaviour of output 1 in case of an internal fault
FOU2 Behaviour of output 2 in case of an internal fault
P-n Switching logic for OUT1: PNP or NPN
diS Update rate and orientation of the display
Uni Unit of measurement for system temperature
rES Restore factory settings
UK
11