Controller board
Table of Contents

Advertisement

Communication Setup - VaporTEK Interface
14. Show Calibration Table: Press '5'
Displays factory set calibration table when connected for the first time; thereafter shows the latest calibrated
table.
15. A/L – Ratio: Press '6'
Sub item 6 can be used to modify the A/L – Ratio. Set A/L – Ratio according to value which is mentioned on
the certificate as K-Factor (110%). NOTE: Set Speed Offset to '0'.
New Connection Hyperterminal
File
Edit
View Call Transfer Help
5. Calibration Table
--------------------
MP
Flow A
Flow B
Speed
[No] [l/min] [l/min] [rpm]
---------------------------
0
0
0
0
1
4
4
80
2
8
8
160
3
12
12
240
4
16
16
320
5
20
20
400
6
24
24
480
7
28
28
560
8
32
32
640
9
36
36
720
10
40
40
800
11
44
44
880
12
48
48
960
13
52
52
1040
14
56
56
1120
15
60
60
1200
Connected 0:02:44
Auto detect
9600-8-N-1
New Connection Hyperterminal
File
Edit
View Call Transfer Help
6. A/L - Ratio
------------------
Recover-Ratio
Speed-Offset
101%
0
do you want to change it [Y/N]? Y
Recover Ratio = 101
new Ratio = 110
Speed Offset = 0
new Offset = 0
Data have been written successfully
Recover-Ratio
Speed-Offset
110%
0
Connected 0:02:44