Commissioning

Note: The communication converter is delivered with the jumper settings "X.21"
and "64 kBit/s".
Open the communication converter
Disconnect the auxiliary supply voltage from both poles.
Open the communication converter. To open the device, you must undo all six cover
screws with a screwdriver.
Configuring the communication converter
The communication converter is configured via jumpers. The slots of the jumpers can be
seen in Figure 19. The factory setting is shown.
Selecting the interface:
Set the jumper X30 in accordance with the interface type selected for communication:
X30 in position 1–2
X30 in position 2–3
Selecting the transmission speed:
With the jumpers for X20, X22, X24 and X26, set the transmission speed necessary for
communication (see table 2). Only one slot can be occupied at any one time.
Note: In the operating mode G.703.1, the jumper must be set to X20, since there is only
one transmission rate for it (64 kBit/s). The transmission rate parameterized in the
protection device for the active interface and the corresponding jumper position
have to correspond to each other.
Jumper →
↓ Transmission
speed
64 kBit/s
128 kBit/s
256 kBit/s
512 kBit/s
Table 2: Jumper for transmission speed
42
DANGER!
Before opening the communication converter, it is absolutely ne-
cessary to isolate it from the auxiliary supply voltage at all poles!
Energized parts pose a potentially lethal hazard!
for interface X.21,
for interface G.703.1.