Siemens 7XV5662-0AA00 Directions For Use Manual page 50

Communication converter - x.21/g.703.1 synchronous interface
Hide thumbs Also See for 7XV5662-0AA00:
Table of Contents

Advertisement

Available languages

Available languages

English
– Fast Transient Disturbance Burst
IEC 60255-22-4, Class A
IEC 61000-4-4, Class IV
– High Energy Surge Voltages (SURGE)
IEC 61000-4-5, Installation Class 3
Power supply
Relay output (GOK)
Communication interfaces
– High Energy Surge Voltages (SURGE)
TBR14 (3), ETS 300046–3 Sect. 5.7.1
Communication interfaces
– Line Conducted HF, amplitude modulated
IEC 61000-4-6, Class III
– Power System Frequency Magnetic Field
IEC 61000-4-8, Class IV
IEC 60255-6
– Oscillatory Surge Withstand Capability
IEEE C37.90.1
– Fast Transient Surge Withstand Capability
IEEE C37.90.1
For life contact if G703.1 port is used,
up to 3 kV burst
– Radiated Electromagnetic Interference
IEEE C37.90.2
– Damped Oscillations
IEC 60694, IEC 61000-4-12
50
4 kV all circuits/2 kV communication,
if guidelines of installation are fullfilled
for life contact if G703.1 port is used,
up to 3 kV burst;
5/50 ns; 5 kHz;
Burst length = 15 ms;
repetition rate 300 ms; both polarities;
= 50 Ω; test duration 1 min
R
i
Impuls: 1.2/50 µs
common mode: 2 kV; 12 Ω; 9 µF
diff. mode: 1 kV; 2 Ω; 18 µF
common mode: 2 kV; 42 Ω; 0.5 µF
common mode: 2 kV; 2 Ω; 18 µF
common mode: 2 kV; 15 Ω; 18 µF
10 V: 150 kHz to 80 MHz; 80 % AM; 1 kHz
30 A/m continuous; 300 A/m for 3 s; 50 Hz
0.5 mT; 50 Hz
2.5 kV (Peak Value); 1 MHz; τ = 15 ms;
400 surges per s; test duration 2 s;
= 150 Ω
R
i
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
repetition rate 300 ms; both polarities;
= 50 Ω; test duration 1 min
R
i
35 V/m; 80 MHz to 1000 MHz
2.5 kV (Peak Value), polarity alternating
100 kHz, 1 MHz, R
7XV5662-0AA00
= 200 Ω
i
C53000-B1174-C134-7

Hide quick links:

Advertisement

Chapters

Table of Contents
loading